Distance Relaying Algorithm for Double-Circuit Transmission Line with Compensation for Reactance Effect under Standard Availability of Measurements

This paper deals with non-pilot distance protection of a double-circuit transmission line. Negative impact of the reactance effect, appearing in measuring a fault loop impedance, on operation of the relay is discussed. An adaptive algorithm allowing one to prevent the relay from mis- or mal-operation caused by the reactance effect is introduced. The algorithm is designed for a standard availability of measurements from one end of the double-circuit line, i.e. when three-phase voltage and current from the faulted line circuit, and additionally zero-sequence current from the healthy line circuit, are provided as the relay input signals. The algorithm is based on changing the position of the distance relay characteristic in such a way that the reactance effect is effectively compensated for. For this purpose the shift vector is determined in on-line relatively simple calculations. The delivered adaptive algorithm has been tested using current and voltage signals obtained from simulation of varies faults using the ATP-EMTP software program. Selected results of the evaluation are presented.

Distance Relaying Algorithm for Double-Circuit Transmission Line with Compensation for Reactance Effect under Standard Availability of Measurements

This paper deals with non-pilot distance protection of a double-circuit transmission line. Negative impact of the reactance effect, appearing in measuring a fault loop impedance, on operation of the relay is discussed. An adaptive algorithm allowing one to prevent the relay from mis- or mal-operation caused by the reactance effect is introduced. The algorithm is designed for a standard availability of measurements from one end of the double-circuit line, i.e. when three-phase voltage and current from the faulted line circuit, and additionally zero-sequence current from the healthy line circuit, are provided as the relay input signals. The algorithm is based on changing the position of the distance relay characteristic in such a way that the reactance effect is effectively compensated for. For this purpose the shift vector is determined in on-line relatively simple calculations. The delivered adaptive algorithm has been tested using current and voltage signals obtained from simulation of varies faults using the ATP-EMTP software program. Selected results of the evaluation are presented.

___

  • J. Izykowski, E. Rosolowski, M. M. Saha, “Postfault analysis of operation of distance protective relays of power transmission lines”, IEEE Transactions on Power Delivery, Vol. 22, No. 1, pp. 74–81, 2007.
  • A. Wiszniewski, “Accurate fault impedance locating algorithm”, IEE Proceedings, Vol. 130, Pt. C, No. 6, pp. 311–315, 1983.
  • L. Eriksson, M. M. Saha, G. D. Rockefeller, “An accurate fault locator with compensation for apparent reactance in the fault resistance resulting from remote-end infeed”, IEEE Transactions on Power Apparatus and Systems, Vol. PAS–104, No.2, pp. 424–436, 1985.
  • Y. Liao, S. Elangovan, “Digital distance relaying algorithm for Şrst zone protection for parallel transmission lines”, IEE Proceedings: Generation, Transmission and Distribution, Vol. 145, No. 5, pp. 531–536, 1998.
  • J. Izykowski, E. Rosolowski, M. M. Saha, “Locating faults in parallel transmission lines under availability of complete measurements at one end”, IEE Proceedings: Generation, Transmission and Distribution, Vol. 151, No. 2, pp. 268–273, 2004.
  • Yi Hu, D. Novosel, M. M. Saha, V. Leitloff, “An adaptive scheme for parallel-line distance protection”, IEEE Transactions on Power Delivery, Vol. 17, No. 1, pp. 105–110, 2002.
  • H. Dommel, ElectroMagnetic Transients Program, BPA, Portland, Oregon, 1986.