A New Relaying Algorithm to Detect Loss of Excitation of Synchronous Generators

A new digital relaying algorithm is introduced for the protection of synchronous generators against loss of excitation conditions. The new algorithm is based on measuring of the 3-phase reactive power output of the machines, and monitors the direction and magnitude of leading reactive power at the generator terminal. The protection algorithm is designed such that it can provide reliable protection against loss of field conditions and remains stable during recoverable power system swing conditions. While the new relay produces a trip signal for partial loss of field conditions causing the machine to lose its stability, it remains stable for the partial loss of field conditions that can be corrected via machine excitation and AVR systems.

A New Relaying Algorithm to Detect Loss of Excitation of Synchronous Generators

A new digital relaying algorithm is introduced for the protection of synchronous generators against loss of excitation conditions. The new algorithm is based on measuring of the 3-phase reactive power output of the machines, and monitors the direction and magnitude of leading reactive power at the generator terminal. The protection algorithm is designed such that it can provide reliable protection against loss of field conditions and remains stable during recoverable power system swing conditions. While the new relay produces a trip signal for partial loss of field conditions causing the machine to lose its stability, it remains stable for the partial loss of field conditions that can be corrected via machine excitation and AVR systems.

___

  • IEEE Committee Report, “IEEE Guide for AC Generator Protection”, Trans. on PWRD, Vol. 4, No. 2, pp.957- , 1989.
  • J. Berdy, “Loss of excitation protection for modern synchronous generators”, IEEE Trans. on PAS, Vol. 94, No.5, pp.1457-1463, 1975.
  • C.R. Mason, “A new loss of excitation relay for synchronous generators”, AIEE Trans., Vol. 68, pp. 1240-1245,
  • D.C. Lee, P. Kundur, R.D. Brown, “A high speed discriminating generator loss of excitation protection”, IEEE Trans. on PAS, Vol. 94, pp. 1865-1899, 1979.
  • R.L. Tremaine, J.L. Blackburn, “Loss of Şeld protection for synchronous machines”, AIEE Trans. on PAS, Vol.73, Part III, pp.765-772, 1954.
  • A.R. Charles, M. Rogers, “A study of loss of excitation relaying and stability of a 595 MVA generator on the Detroit Edison System”, IEEE Trans. on PAS, Vol. 94, No. 5, pp. 1449-1456, 1975.
  • IEEE Working Group Report, “Loss of Field Relay Operation during System Disturbances”, IEEE Trans. On PAS, Vol.5, pp.1464-1472, 1975.
  • P.O. Bobo, J.W. Skooglund, C.L. Wanger, “Performance of excitation systems under abnormal conditions”, IEEE Trans. on PAS, Vol. 87, No. 2, pp. 547-553, 1968.
  • H.G. Darron, J.L. KoepŞnger, J.R. Mather, P.A. Rusch, “The influence of generator loss of excitation on bulk power system stability”, IEEE Trans. on PAS, Vol. 96, No. 5, pp. 1473-1483, 1975.
  • P. Kundur, Power System Stability and Control, Vol. I , New York, McGraw-Hill Inc., 1993.
  • A.E. Fitzgerald et al, Electric Machinery, New York, McGraw-Hill Inc., 1992
  • IEEE Committee Report, “Survey of Experience with Generator Protection and Prospects for Improvements Using Digital Computer”, IEEE Trans. on PWRD, Vol. 3, No. 4, pp. 1511-1521, 1988.
  • M.A. Redfern, M.J. ChecksŞeld, “A new pole slipping protection algorithm for dispersed storage and generators using equal area criterion”, IEEE Trans. on PD, Vol.10, No.1, pp.194-202, 1995.
  • O. Usta, M. Bayrak, “A new digital relay for generator protection against asymmetrical faults”, IEEE Trans. on PWRD, Vol. 17, No. 1, pp. 54-59, 2002.
  • M.A. Redfern, O. Usta, G. Fielding, E.O. Walker, “Power based algorithm to provide loss of grid protection for embedded generation”, IEE Proceedings on Generation Transmission and Distribution, Vol. 141, No. 6, pp. 1646, 1994.
  • J.M. Aller et al, “Advantage of Instantaneous Reactive Power DeŞnition”, IEEE Power Engineering Review, Vol. 19, No. 6, pp. 54-56, June 1999.
  • M.H. Musa, Design of new reactive power based digital relaying algorithm for protection of generator against loss of Şeld current, Ph.D. thesis, ITU, Istanbul, 2002. APPENDIX
  • Generator parameters: Rated voltage:24 kV Rated power:991 MVA at cos ϕ = 0.8 Rated excitation current:1640 A xd= 1.15 pu, xq= 0.685 pu, xd = 0.31 pu, xq = 0.68 pu, xd= 0.21 pu, xq= 0.182 pu
  • Transformer rated power:1300 MVA
  • For each transmission line:r = 4.74 ohm, x = 21.34 ohm. Automatic Voltage Regulator: VT Vmax V min Ks fs +Ts f Ka= 250 Kf= 0.04 Te= 0.04 Tr= 0.015