Fast adaptive reclosing in double-circuit transmission lines for improving power system stability based on harmonic analysis scheme
Fast adaptive reclosing in double-circuit transmission lines for improving power system stability based on harmonic analysis scheme
An appropriate method is proposed for identifying permanent faults from transient faults in double-circuittransmission lines. This method could be used in adaptive single phase auto-reclosures in order to diagnose betweenpermanent and transient faults, determine extinguishing time of the secondary arc, and calculate issuing time of reclosingcommands during the occurrence of transient single phase to ground faults. The proposed method is based on harmonicanalysis of the adjacent healthy circuit and could be an effective solution for blocking permanent disconnection of thepower flow, improving stability, and maintaining the power network synchronism. In this paper, transient and permanentfaults are simulated on a typical power system, and then current harmonics of the healthy circuit terminal are extractedand finally the proposed index for identifying the fault type is applied. In the case of transient faults, this methoddetermines the minimum time needed for a fast successful adaptive reclosing in the network and thus prevents instabilityand nonsynchronism in both sides of the transmission line. Results of the various simulations run in EMTP-RV verifiesaccurate performance of the proposed approach.
___
- [1] Jannati M, Vahidi B, Hosseinian SH, Ahadi SM. A novel approach to adaptive single phase auto-reclosing scheme
for EHV transmission lines. International Journal of Electrical Power & Energy Systems 2011; 33 (3): 639-646. doi:
10.1016/j.ijepes.2010.12.023
- [2] Wang X, Yang J, Liu P, Liu W, Yan J et al. Online calculation for the optimal reclosing time of transmission lines.
Electric Power Components and Systems 2016; 44 (17): 1-13. doi: 10.1080/15325008.2016.1199071
- [3] Jannati M, Jazebi S, Vahidi B, Hosseinian SH. A novel algorithm for fault type fast diagnosis in overhead transmission lines using hidden markov models. Journal of Electrical Engineering & Technology 2011; 6 (6): 742-749.
doi: 10.5370/JEET.2011.6.6.742
- [4] Radojevic ZM, Shin JR. New digital algorithm for adaptive reclosing based on the calculation of the faulted
phase voltage total harmonic distortion factor. IEEE Transactions on Power Delivery 2007; 22 (1): 37-41. doi:
10.1109/TPWRD.2006.886781
- [5] Aggarval RK, Johns AT, Dunn RW, Fitton DS. Neural network based adaptive single-pole autoreclosure technique
for EHV transmission system. IEE Proceedings - Generation, Transmission and Distribution 1994; 141 (2): 155-160.
doi: 10.1049/ip-gtd:19949864
- [6] Yu IK, Song YH. Wavelet transform and neural network approach to developing adaptive single-pole auto-reclosing
scheme for EHV transmission system. IEEE Power Engineering Review 1998; 18 (11): 62-64. doi: 10.1109/39.726911
- [7] Radojevic ZM, Shin JR. New one terminal digital algorithm for adaptive reclosing and fault distance calculation on transmission lines. IEEE Transactions on Power Delivery 2006; 21 (3): 1231-1237. doi: 10.1109/TPWRD.2005.860285
- [8] Elkalashy NI, Darwish HA, Taalab AI, Izzularab MA. An adaptive single pole autoreclosure based on
zero sequence
power. Electric Power System Research 2007; 77 (5): 438-446. doi: 10.1016/j.epsr.2006.04.006
- [9] Lin X, Weng H, Liu H, Lu W, Liu P et al. A novel adaptive single-phase reclosure scheme using dual-window
transient energy ratio and mathematical morphology. IEEE Transactions on Power Delivery 2006; 21 (4): 1871-
1877. doi: 10.1109/TPWRD.2006.881427
- [10] Yaozhong G, Fanghai S, Yuan X. Prediction method for preventing single-phase reclosing on permanent fault. IEEE
Transactions on Power Delivery 1989; 4 (1): 114-121. doi: 10.1109/61.19197
- [11] Quoc TT, Hadj-Said N, Sabonnadiere JC, Feuillet R. Reducing dead time for single-phase auto-reclosing on a
series-capacitor compensated transmission line. IEEE Transactions on Power Delivery 2000; 15 (1): 51-56. doi:
10.1109/61.847228
- [12] Suonan JL, Sun DD, Fu W, Wang XB, Liu WT et al. Identification of permanent faults for single-phase autoreclosure on transmission lines with shunt reactors. In: Proceedings of CSEE; Oahu, HI, USA; 2006. pp. 75–81. doi:
10.1109/tpwrd.2009.2014475
- [13] Chothani NG, Bhalja BR, Desai AK. A new algorithm for coordination of relay and auto-reclosure in 220
kV transmission system. In: India Conference (INDICON); Mumbai, India; 2013. pp. 1-6. doi: 10.1109/INDCON.2013.6726062
- [14] Haitao Z, Chen Ping, Li-Ping W. Adaptive reclosure technology for high-voltage overhead lines combined with
underground power cables based on travelling wave principle. In: Proceedings of the 2012 International Conference
on Communication, Electronics and Automation Engineering; Xi’an, China; 2012. pp. 143–150
- [15] Adly AR, Sehiemy RA, Abdelaziz AY. An optimal/adaptive reclosing technique for transient stability enhancement
under single pole tripping. Electric Power Systems Research 2017; 151: 348-358. doi: 10.1016/j.epsr.2017.06.005
- [16] Seo H, Rhee S. Novel adaptive reclosing scheme using wavelet transform in distribution system with battery
energy storage system. International Journal of Electrical Power & Energy Systems 2018; 79: 186-200. doi:
10.1016/j.ijepes.2017.11.009
- [17] Shao W, Liu Y, Zhang W. Nonfault detection for three-phase reclosure in reactor-compensated transmission lines
based on fault location. In: 5th International Conference on Electric Utility Deregulation and Restructuring and
Power Technologies (DRPT); Changsha, China; 2015. pp. 1-4. doi: 10.1109/DRPT.2015.7432370
- [18] Jiaxing N, Baina H, Zhenzhen W, Jie K. Algorithm for adaptive single-phase reclosure on shunt-reactor compensated
extra high voltage transmission lines considering beat frequency oscillation. IET Generation, Transmission &
Distribution 2018; 12 (13): 3193-3200. doi: 10.1049/iet-gtd.2017.1175
- [19] Xie X, Huang C. A novel adaptive auto-reclosing scheme for transmission lines with shunt reactors. Electric Power
Systems Research 2019; 171: 47-53. doi: 10.1016/J.EPSR.2019.01.028
- [20] Luo X, Huang Ch, Jiang Y, Guo S. An adaptive three-phase reclosure scheme for shunt reactor-compensated
transmission lines based on the change of current spectrum. Electric Power Systems Research 2018; 158: 184–194.
doi: 10.1016/J.EPSR.2018.01.011
- [21] Nikoofekr I, Sadeh J. Determining secondary arc extinction time for single-pole auto-reclosing
based on harmonic
signatures. Electric Power Systems Research 2018; 163: 211-225. doi: 10.1016/j.epsr.2018.06.013
- [22] Abedini M, Sanaye-Pasand M, Davarpanah M, Lesani H, Shahidehpour M. Predictive auto-reclosure approach to
enhance transient stability of grid-connected DGs. IET Generation, Transmission & Distribution 2019; 13 (14):
3011–3019. doi: 10.1049/iet-gtd.2018.6455
- [23] Hernández JC, Ruiz-Rodriguez FR, Jurado F. Technical impact of photovoltaic-distributed generation on radial
distribution systems: stochastic simulations for a feeder in Spain. International Journal of Electrical Power &
Energy Systems 2013; 50: 25-32. doi: 10.1016/j.ijepes.2013.02.010
- [24] Monadi M, Hooshyar H, Vanfretti L. Design and real-time implementation of a PMU-based adaptive autoreclosing
scheme for distribution networks. International Journal of Electrical Power & Energy Systems 2019; 105: 37-45.
doi: 10.1016/J.IJEPES.2018.07.064
- [25] Dias O, Tavares MC, Magrin F. Hardware implementation and performance evaluation of the fast adaptive singlephase auto reclosing algorithm. Electric Power Systems Research 2019; 168: 169-183. doi: 10.1016/j.epsr.2018.11.019
- [26] Shang L. Fault nature identification for single-phase adaptive reclosure on double circuit EHV transmission lines
with shunt reactors. In: International Conference on High Voltage Engineering and Application; New Orleans, LA,
USA; 2010. pp. 1-4. doi: 10.1109/ichve.2010.5640714
- [27] Kizilcay M, Ban G, Prikler L, Handl P. Interaction of the secondary arc with the transmission system during singlephase autoreclosure. In: IEEE Bologna Power Tech Conference Proceedings; Bologna, Italy; 2003. pp. 1-20. doi:
10.1109/PTC.2003.1304294
- [28] Prikler L, Kizilcay M, Ban G, Handle P. Improved secondary arc models based on identification of arc parameters
from staged fault test records. In: 14PSCC; Seville, Spain; 2002. pp. 1-7
- [29] Kizilcay M, Koch KH. Numerical fault arc simulation based on power m tests. European Transactions on Electrical
Power 1994; 4 (3): 177-186. doi: 10.1002/etep.4450040302
- [30] Johns AT, Aggarwal RK, Song YH. Improved techniques for modeling fault arcs on faulted EHV transmission
systems. IEE Proceedings - Generation, Transmission and Distribution 1994; 141 (2): 148-154. doi: 10.1049/ipgtd:19949869